Examples#

A minimum network model is included as an example in version 35 of both formats RAW and RAWX.

 0,      100.0, 35, 0, 0, 60.00       / October 27, 2020 18:37:53
 PSS(R)E Minimum RAW Case

0 / END OF SYSTEM-WIDE DATA, BEGIN BUS DATA
    1,'Slack-Bus   ', 138.0000,3
    2,'Load-Bus    ', 138.0000,1
0 / END OF BUS DATA, BEGIN LOAD DATA
    2,'1 ',1,,,   40.000,    15.000
0 / END OF LOAD DATA, BEGIN FIXED SHUNT DATA
0 / END OF FIXED SHUNT DATA, BEGIN GENERATOR DATA
    1,'1 ',   40.350,   10.870
0 / END OF GENERATOR DATA, BEGIN BRANCH DATA
    1,     2,'1 ', 0.01938, 0.05917,0.05280
0 / END OF BRANCH DATA, BEGIN SYSTEM SWITCHING DEVICE DATA
0 / END OF SYSTEM SWITCHING DEVICE DATA, BEGIN TRANSFORMER DATA
0 / END OF TRANSFORMER DATA, BEGIN AREA DATA
0 / END OF AREA DATA, BEGIN TWO-TERMINAL DC DATA
0 / END OF TWO-TERMINAL DC DATA, BEGIN VOLTAGE SOURCE CONVERTER DATA
0 / END OF VOLTAGE SOURCE CONVERTER DATA, BEGIN IMPEDANCE CORRECTION DATA
0 / END OF IMPEDANCE CORRECTION DATA, BEGIN MULTI-TERMINAL DC DATA
0 / END OF MULTI-TERMINAL DC DATA, BEGIN MULTI-SECTION LINE DATA
0 / END OF MULTI-SECTION LINE DATA, BEGIN ZONE DATA
0 / END OF ZONE DATA, BEGIN INTER-AREA TRANSFER DATA
0 / END OF INTER-AREA TRANSFER DATA, BEGIN OWNER DATA
0 / END OF OWNER DATA, BEGIN FACTS CONTROL DEVICE DATA
0 / END OF FACTS CONTROL DEVICE DATA, BEGIN SWITCHED SHUNT DATA
0 / END OF SWITCHED SHUNT DATA, BEGIN GNE DEVICE DATA
0 / END OF GNE DEVICE DATA, BEGIN INDUCTION MACHINE DATA
0 / END OF INDUCTION MACHINE DATA, BEGIN SUBSTATION DATA
0 / END OF SUBSTATION DATA
Q
{
     "network":{
         "caseid":{
             "fields":["ic", "sbase", "rev", "xfrrat", "nxfrat", "basfrq", "title1"],
             "data":[0, 100.00, 35, 0, 0, 60.00, "PSS(R)E Minimum RAWX Case"]
         },
         "bus":{
             "fields":["ibus", "name", "baskv", "ide"],
             "data":[
                 [1, "Slack-Bus", 138.0, 3],
                 [2, "Load-Bus", 138.0 1]
             ]
         },
         "load":{
             "fields":["ibus", "loadid", "stat", "pl", "ql"],
             "data":[
                 [2, "1", 1, 40.0, 15.0]
             ]
         },
         "generator":{
             "fields":["ibus", "machid", "pg", "qg"],
             "data":[
                 [1, "1", "40.35", "10.87"]
             ]
         },
         "acline":{
             "fields":["ibus", "jbus", "ckt", "rpu", "xpu", "bpu"],
             "data":[
                 [1, 2, "1", 0.01938, 0.05917, 0.05280]
             ]
         }
    }
}